Part Number Hot Search : 
8M161RB 0241H1D2 30100 007AT A12BB RT1P237 T131003 CY14B
Product Description
Full Text Search
 

To Download RT500 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  page 1/4 11december2013/version 2 lem reserves the right to carry out modifcations on its transducers, in order to improve them, without prior notice www.lem.com rt 500 flexible split-core rogowski coil for the electronic measurement of ac waveform currents, with galvanic separation between the primary circuit (power) and the secondary circuit (measurement). the patented perfect loop technology defnitely solves the problem of the rogowski coil opening by introducing a specifc magnetic device. this dramatically reduces both the error due to the position of the measured conductor within the sensor, and the error due to the proximity of external conductors. electrical data i pn primary nominal rms current 500 a m mutual inductance transfer ratio 1) ( 5 %) 0.064 h v out output voltage (instantaneous) 2) v out = m v v out output voltage (sinusoidal wave) 2) v out = 2 m f i p ac v example: @ 50 hz, 500 a v out = 2 64 10 -9 50 500 = 10.05 mv l s coil inductance ( 5 %) 125 h r s coil resistance t a = 20 c typical 40 ? high cut-off frequency 2) 700 khz accuracy - dynamic performance data l linearity error none tcm temperature coeffcient of m 30 ppm/k p positioning error 3) max 0.65 % general data t a ambient operating temperature (90 % rh) - 10 .. + 65 c t s ambient storage temperature - 25 .. + 70 c m mass 85 g ipxx protection degree ip 2x standards safety iec 61010-1: 2001 2nd edition iec 61010-2-032: 2002 iec 61010-031: 2002 + amd 1: 2008 notes: 1) lem provides uncalibrated coils with up to 5 % manufacturing tolerance. calibration must be performed within the fnal application. 2) open circuit condition (no load). 3) considering a primary conductor of at least ? 15 mm perpendicular to the rt loop. features split core type ? 70 mm sensing aperture for non-contact measurement 1.5 m output cable insulating plastic case recognized according to ul 94-v0. advantages thin, lightweight and fexible easy installation suitable even for the most confned spaces very low positioning error. applications power meters current measurement for active power calculation. energy sub-meters for energy effciency monitoring, consumption analysis and costs allocation. power quality monitoring condition monitoring (e.g. motor loads such as conveyers, pumps or hvac). distributed measurement systems. application domain energy solutions. d i p d t n 97.f9.50.000.0
page 2/4 11december2013/version 2 lem reserves the right to carry out modifcations on its transducers, in order to improve them, without prior notice www.lem.com ul 61010-1: ratings and assumptions of certifcation file # e330077-a2-ul standards can/csa-c22.2 no. 61010-1, 2nd edition, 2004-07 (electrical equipment for measurement, control, and laboratory use; part 1: general requirements) ul 61010-1, 2nd edition, 2005-07-22 (electrical equipment for measurement, control, and laboratory use; part 1: general requirements) ratings parameter symbol unit value primary involved potential v ac/dc 300 max surrounding air temperature t a c 50 primary current i p a according to series primary current output voltage v out v ac 0 to 30 conditions of acceptability for use only in or with complete equipment where the acceptability of the combination is determined by underwriters laboratories inc. when installed in an end-product, consideration must be given to the following: 1 - this component has been judged on the basis of the creepage and clearances required in the indicated standards, which would cover the component itself if submitted for listing: ul 61010-1 2nd ed., can/csa 22.2 no 61010-1 2nd ed. 2 - the need for the following shall be considered in the end-product: markings and documentation that comply with clause 5. 3 - the following tests shall be performed in the end-product evaluation: dielectric strength. 4 - the unit is considered acceptable for use in a max ambient of: 50 c. marking only those products bearing the ur mark should be considered to be recognized and covered under ul's follow-up service. always look for the mark on the product.
page 3/4 11december2013/version 2 lem reserves the right to carry out modifcations on its transducers, in order to improve them, without prior notice www.lem.com rt 500 insulation coordination u b rated insulation rms voltage 1) 300 v with iec 61010-1 standards following conditions: - reinforced insulation - over voltage category cat iii - pollution degree pd2 - heterogeneous feld u d rms voltage for ac insulation test 2) , 50 hz, 1 min 3.5 kv ? w impulse withstand voltage 1.2/50 s 6.5 kv min d cp creepage distance 6 mm d ci clearance 6 mm cti comparative tracking index (group i) 3) 600 v notes: 1) between primary conductor and ground. if insulated cable is used for the primary circuit, the voltage category could be improved according to the primary cable insulation category (please refer to the cable manufacturers indications). 2) between primary (completely flling the hole) and secondary 3) plastic parts. safety and warning notes in order to guarantee safe operation of the transducer and to be able to make proper use of all features and functions, please read these instructions thoroughly! safe operation can only be guaranteed if the transducer is used for the purpose it has been designed for and within the limits of the technical specifcations. ensure you get up-to-date technical information that can be found in the latest associated datasheet under www.lem.com. caution! risk of danger ignoring the warnings can lead to serious injury and/or cause damage! the electric measuring transducer may only be installed and put into operation by qualifed personnel that have received an appropriate training. the corresponding national regulations shall be observed during installation and operation of the transducer and any electrical conductor. the transducer shall be used in electric/electronic equipment with respect to applicable standards and safety requirements and in accordance with all the related systems and components manufacturers operating instructions. caution! risk of electrical shock when operating the transducer, certain parts of the module may carry hazardous live voltage (e.g. primary conductor). the user shall ensure to take all measures necessary to protect against electrical shock. the transducer is a build-in device containing conducting parts that shall not be accessible after installation. a protective enclosure or additional insulation barrier may be necessary. installation and maintenance shall be done with the main power supply disconnected except if there are no hazardous live parts in or in close proximity to the system and if the applicable national regulations are fully observed. safe and trouble-free operation of this transducer can only be guaranteed if transport, storage and installation are carried out correctly and operation and maintenance are carried out with care.
page 4/4 11december2013/version 2 lem reserves the right to carry out modifcations on its transducers, in order to improve them, without prior notice www.lem.com dimensions rt 500 (in mm) mechanical characteristics general tolerance 1 mm output cable length 3000 mm warning! do not stress the coil by applying any kind of mechanical force (ie. twisting, puncturing, excessive pressure, tight bending, etc.) which will dramatically degrade the devices accuracy. connection remarks v out = v s+ - v s- is positive when d i p /dt fows in the direction of the arrow (see fg. 1) due to low positioning error ( p ), the device does not need to be physically fastened around the primary conductor. should the device be secured, make sure no mechanical stress is applied to the coil itself. fig. 1 i p i p v s+ v s-


▲Up To Search▲   

 
Price & Availability of RT500

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X